Energy Summary
|
188
|
m2 Treated Floor Area (TFA)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Value
|
Units
|
Value
|
Units
|
Value
|
Units
|
Share
|
Annual Demand
|
|
|
|
|
|
|
|
1
|
Annual Heating Energy Demand
|
3486
|
kWh
|
12.5
|
GJ
|
11894
|
million btu (MMBtu)
|
|
|
Specific Heating Energy Demand
|
18.5
|
kWh/m²
|
0.1
|
GJ
|
63
|
million btu (MMBtu)
|
|
|
PHIUS Specific Heating demand Threshold
|
15.1
|
kWh/m²
|
|
|
4.8
|
|
|
2
|
Annual Cooling Energy Demand
|
287
|
kWh
|
1.0
|
GJ
|
979
|
million btu (MMBtu)
|
|
|
Specific Cooling Energy Demand
|
1.5
|
kWh
|
|
GJ
|
5
|
million btu (MMBtu)
|
|
|
PHIUS Specific Cooling demand Threshold
|
12.0
|
W/m²
|
|
|
3.8
|
|
|
3
|
Energy provided by earth tube
|
3850
|
kWh
|
13.9
|
GJ
|
13136
|
million btu (MMBtu)
|
|
4
|
Heating/cooling energy provided by postheater
|
1743
|
kWh
|
6.3
|
GJ/h
|
5947
|
BTU/h
|
25%
|
5
|
Heating/cooling energy provided by CERV (@ COP=3)
|
2030
|
kWh
|
7.3
|
GJ/h
|
6926
|
BTU/h
|
|
6
|
annual CERV energy consumption
|
1216
|
kWh
|
4.4
|
GJ/h
|
4149
|
BTU/h
|
17%
|
7
|
Annual DHW Energy
|
3348
|
kWh
|
12.1
|
GJ
|
11422
|
million btu (MMBtu)
|
|
8
|
Energy consumption of Midea Heat Pump, COP=3.6)
|
930
|
kWh
|
3.3
|
GJ
|
3173
|
million btu (MMBtu)
|
13%
|
9
|
Total Lighting & Plug Loads
|
3173
|
kWh
|
11.4
|
GJ/h
|
10827
|
BTU/h
|
45%
|
|
Total Annual Energy Consumption (column 4 + 6 + 8 + 9)
|
7062
|
kWh
|
25.4
|
GJ
|
24096
|
million btu (MMBtu)
|
100%
|
|
Primary energy limit: 4200 kWh/person/yr x 4
|
16800
|
kWh
|
|
|
|
|
|
|
PHIUS site energy limit = 16,800 kWh / 2.05 source energy multiplier for Canada per PHIUS+2018
|
8195
|
kWh
|
> than
|
7062
|
kWh
|
|
|
|
|
|
|
|
|
|
|
|
Max Heating Load
|
2660
|
W
|
0.010
|
GJ/h
|
9076
|
|
100%
|
|
Area specific heating load
|
14.1
|
W/m²
|
|
|
4.5
|
|
|
|
PHIUS Specific Heat Load Threshold
|
15.1
|
W/m²
|
|
|
4.8
|
|
|
2
|
Max heating load provided by Earth Tube
|
990
|
W
|
|
3378
|
BTU/h
|
37%
|
3
|
CERV heating at 0 degrees Celcius
|
1000
|
W
|
|
|
3412
|
BTU/h
|
38%
|
4
|
Supplementary heat from Post Heater
|
670
|
W
|
0.002
|
GJ/h
|
2286
|
BTU/h
|
25%
|
5
|
Heating load transportable by the supply air (250cfm)
|
3465
|
W
|
less than
|
2660
|
|
|
|
6
|
Area specific cooling load
|
1.2
|
W/m²
|
|
|
0.4
|
|
|
7
|
PHIUS Specific cooling Load Threshold
|
5.7
|
W/m²
|
|
|
1.8
|
|
|
8
|
Radiant floor system flow rate
|
-
|
LPM =
|
#VALUE!
|
gpm
|
|
|
|
9
|
Max DHW Demand (2 hr)
|
45
|
gpm
|
171
|
Lpm
|
|
|
|
|
|
|
|
|
|
Predicted energy costs
Est. Propane Consumption (L)
|
0
|
Litres
|
|
Est. Electricity Consumption (kWh)
|
7062
|
kWh
|
|
Est. Annual Operating Expenses ($/yr)
|
|
|
|
Est. Annual Propane Cost:
|
0.9
|
$/Litre
|
$ -
|
Est. Annual Elec. Cost:
|
0.16
|
$/kWh
|
$ 1,130
|
Total utility cost per year
|
|
|
$ 1,130
|
PHIUS Local Climate-Specific Thresholds.
- ASHRAE 2013 & Global Solar Radiation Location = London, ON Airport, Zone 5
- Annual heating demand 6.6 kBtu/sf-iCFA.yr x 3.155 = 20.8 kWh/m2/yr
- Annual cooling demand 1.8 kBtu/sf-iCFA.yr x 3.155 = 5.68 kWh/m2/yr
- Peak heating load = 4.8 BTU/sf-iCFA.h x 3.1546 = 15.1 Watt/Square Meter (W/m²)
- Peak cooling load = 3.8 Btu/sf-iCFA.h x 3.1546 = 12.0 Watt/Square Meter (W/m²)
- PHIUS Recommended max window U value = 0.14 Btu/h.sf.F